4.6.6. The manual fire alarm boxes forming part of an electrical fire alarm system shall be so installed that:
(a)  from any part of a floor area, it is not necessary to travel more than 60 m to reach a manual fire alarm box on the same floor; and
(b)  a fire alarm box is located within 7.5 m from any exit of the floor area.